Digital insulation testing up to 5000 volts
The Fluke 1550B is a digital insulation tester capable of testing switchgear, motors, generators and cables at up to 5000 V DC. It can be used for a wide range of tests: from simple spot checks to timed tests and breakdown tests. Measurement storage and PC interface software make it ideal for preventive maintenance. Heavy-duty leads, probes and alligator clips fit in the custom carrying case, for a rugged field testing kit.
General Features:
- Test voltages of 250V, 500 V, 1000 V, 2500 V, and 5000 V
- Capable of testing in 50V increments between 250V and 1000V and 100V increments between 1000V and 5000V
- Measures 0 to 1 Tera-Ohm
- Warning voltage function alerts the user that line voltage is present and gives the voltage reading up to 600 V AC or DC
- Guard system eliminates the effect of surface leakage current on high-resistance measurements
- Large digital/analog LCD shows detailed measurement data
- Cable or insulation capacitance
- Leakage current
- Ramp function (0-5000 V DC) for breakdown testing
- Timer 1 to 99 minutes
- Polarization index and dielectric absorption calculated automatically
- 99 memory locations store all measurements parameters
- Includes Quicklink 1550B Software and Optical Interface cable
- Two year warranty

Specifications
| Test Voltage 250 V DC | | Range: | 200 kΩ to 5 GΩ | | Accuracy: | 5% | | Range: | 5 GΩ to 50 GΩ | | Accuracy: | 20% | |
| Test Voltage 500 V DC | | Range: | 200 kΩ to 10 GΩ | | Accuracy: | 5% | | Range: | 10 GΩ to 100 GΩ | | Accuracy: | 20% | |
| Test Voltage 1000 V DC | | Range: | 200 kΩ to 20 GΩ | | Accuracy: | 5% | | Range: | 20 GΩ to 200 GΩ | | Accuracy: | 20 | |
| Test Voltage 2500 V DC | | Range: | 200 kΩ to 50 GΩ | | Accuracy: | 5% | | Range: | 50 GΩ to 500 GΩ | | Accuracy: | 20% | |
| Test Voltage 5000 V DC | | Range: | 200 kΩ to 100 GΩ | | Accuracy: | 5% | | Range: | 100 GΩ to 1 TΩ | | Accuracy: | 20% | |
| Short circuit current | |
| Bar graph | |
| Insulation test voltage | | Accuracy: | 0% to 10% at 1 mA load current | |
| Induced AC mains current rejection | |
| Charging rate for capacitive load | |
| Leakage current | | Range: | 1 nA to 2 mA | | Accuracy: | ±(5% + 2 nA) | |
| Capacitance measurements | | Range: | 0.01 µF to 15.00 µF | | Accuracy: | ±(15% rdg + 0.03 µF) | |
| Live circuit indicator | | Range: | 30 V to 600 V (AC/DC, 50/60 Hz) | | Accuracy: | ±(5% + 2V) | |
| Timer | | | 1 - 99 minutes | | Settable: | 1 minute increments | | Indication: | 1 second resolution | |
| Ramp | | | 0% to 100% of selected test voltage, or until breakdown | |
Environmental Specifications
Safety Specifications
Mechanical & General Specifications
| Size | | | 170mm x 242mm x 330 mm (6.7" x 9.5" x 13.0") | |
| Weight | | | 4 kg (with battery) (8.8 lbs) | |
| Batteries | | | 12 V, lead-acid, rechargeable | |
| Warranty | |
| Battery Life | | Test voltage: | Number of tests | | 250 V: | 4100 | | 500 V: | 3600 | | 1000 V: | 3200 | | 2500 V: | 2500 | | 5000 V: | 1500 | |
| Shock & Vibration | |
| Charger input | | AC: | 85 to 250 V AC, 50/60 Hz, 50 VA | |
| Safety Rating | | | EN 61010-1, CAT III 600V, EN61557, Parts 1 & 2 | |
| EMI immunity | |
| Operating Temperature | | | -20°C to +50°C (-4°F to 122°F) | |
| Storage Temperature | | | -20 °C to +65 °C (-4°F to 149°F) | |
| Humidity (Without Condensation) | | | 80% at 31 °C (87.8°F), 50% at 50 °C (122°F) | |
| Dust/water resistance | |
| Operating Altitude | |